ABB S800 I/O is a comprehensive, distributed and modular process I/O system that communicates with parent controllers over industry-standard field buses. Thanks to its broad connectivity it fits a wide range of process controllers from ABB and other vendors.
By permitting installation in the field, close to sensors and actuators, S800 I/O reduces the installation cost by reducing the cost of cabling. And thanks to features such as “hot swap” of modules, “on-line” reconfiguration and redundancy options, it contributes to keeping production-and thereby profits-up.
General specifications
Communication interfaces
CI810 For Advant Fieldbus 100. Supports dual bus-cable redundancy. With AC 400 series controllers.
CI801 For PROFIBUS-DP/V1. Hot Configuration in Run & HART pass-through. GSD-file provided.
TB820V2 Optical cluster modem for Modulebus/drives integration.
TB825 Optical media converter. Multimode up to 1 000 meter.
TB826 Long range optical media converter. Single mode up to 5 000 meter.
TB810 / 811 / 842 Modulebus optical port.
Redundant interface
CI820 For redundant Advant Fieldbus 100 in combination with Advant Controller 400 series controllers.
TB815 Interconnection Unit. An electrical and optical Modulebus interface for coordination of the two
parallell CI820 needed.
CI840A For redundant PROFIBUS-DP/V1. Hot Configuration in Run & HART pass-through. GSD file provided.
TB840A Optical cluster modem for redundant optical Modulebus. Installed on TU840/TU841/TU848/TU849.
Use TU807 for single configuration. Used with AC 800M. Hot Conf In Run, HART pass-through and
Sequence of Events. Installation on vertical DIN rail.
Module Termination Units (MTU:s)
TU810V1 With screw terminals
TU812V1 With 25 pin D-sub connector
TU814V1 With 3 crimp snap-in connectors
TU818 With screw terminals
TU819 With dual 25 pin D-sub
TU811V1 With screw terminals
TU813 With 3 crimp snap-in connectors
Compact for intrinsic safety
TU89X With screw terminals & isolated power supply
Extended, 50 V applications
TU830V1 / TU835V1 / TU838 / TU850 With screw terminals, pwr. distribution & fuse
TU833 With spring-cage term., pwr. distribution & fuse
TU834 With screw terminals for shunt sticks, TY80X
TU831V1 / TU836V1 / TU837V1 / TU839 / TU851 With screw terminals, pwr. distribution & fuse
TU842 / 843 (horiz./vert. mounting) with screw terminals
TU844 / 845 (horiz./vert. mounting) with screw terminals and shunt sticks, TY80X
TU852 / 854 (horiz./ver. mounting) with 25 pin D-subs and shunt sticks, TY80X
TU805 For DI801 & DO801. With field power distribution screw terminals
S800 I/O modules
Digital input modules
DI810 Digital input. 16 ch., 2 groups of 8 ch., 24 V d.c., current sink.
DI811 Digital input. 16 ch., 2 groups of 8 ch., 48 V d.c., current sink.
DI814 Digital input. 16 ch., 2 groups of 8 ch., 24 V d.c., current source.
DI818 Digital input. 32 ch., 2 groups of 16 ch., 24 V d.c., current sink.
DI820 Individually galvanic isolated channels. 8 ch., separate returns, 110 V d.c., 120 V a.c.
DI821 Individually galvanic isolated channels. 8 ch., separate returns, 220 V d.c., 230 V a.c.
DI825 Individually galvanic isolated channels
with SOE (Sequence Of Events).
8 ch., separate returns, 125 V d.c.
DI828 Digital input. 16 ch., separate returns, 110 V d.c., 120 V a.c / d.c.
DI830 With SOE (Sequence Of Events). 16 ch., 2 groups of 8 ch., 24 V d.c., current sink. Event recording resolution: <0.5 ms.
DI831 With SOE (Sequence Of Events). 16 ch., 2 groups of 8 ch., 48 V d.c., current sink. Event recording resolution: <0.5 ms.
DI885 With SOE (Sequence Of Events) &
wire-fault detection.
8 ch., 1 group of 8 ch., 24-48 V d.c., current sink. Event recording resolution: 1 ms.
Pulse input module
DP820 Individually galvanic isolated
channels.
2 ch., separate returns, signal voltage: RS422/5 V/12 V/24 V/13 mA d.c., freq. measurement or pulse
counting 0.25 Hz - 1.5 MHz
Digital output modules
DO810 Digital output. 16 ch., 2 groups of 8 ch., 24 V d.c., max 0.5 A, transistor, current source, short-circuit-proof.
DO814 Digital output. 16 ch., 2 groups of 8 ch., 24 V d.c., max 0.5 A, transistor, current sink, short-circuit-proof.
DO815 With wire-fault detection. 8 ch., 2 groups of 4 ch., 24 V d.c., max 2 A, transistor, current source, short-circuit-proof.
DO818 Digital output. 32 ch., 2 groups of 16 ch., 24 V d.c., max 0.5 A, transistor, current source, short-circuit-proof .
DO820 Individually galvanic isolated channels. 8 ch., separate returns, 5-250 V, max 3 A a.c./d.c., relay (N.O.).
DO821 Individually galvanic isolated channels. 8 ch., separate returns, 5-250 V, max 3 A a.c./d.c., relay (N.C.).
DO828 Individually galvanic isolated channels. 16 ch., separate returns, 5-250V a.c. / 5-125V d.c. max 2A a.c./d.c., relay (N.O.).
Analog input modules
AI810 Analog input. 8 ch., 1 group of 8 ch., single ended with common return, 0(4)-20 mA, 0(2)-10 V, 12 bits.
AI815 With HART interface. 8 ch., 1 group of 8 ch., single ended with common return, 0(4)-20 mA 0(1)-5 V, 12 bits, HART interface,
transmitter power supply.
AI820 Differential inputs. 4 ch., 1 group of 4 ch., bipolar differential, ±0(1)-5 V, ±0(2)-10 V, ±0(4)-20 mA, 14 bits + sign.
AI825 Individually galvanic isolated channels. 4 ch., separate returns, isolated bipolar, ±0(2)-10 V, ±0(4)-20 mA, 14 bits + sign.
AI830A RTD inputs with wire-fault detection. 8 ch., 1 group of 8 ch., Pt100, Ni100, Ni120, Cu10, resistor 0-400 Ω, 14 bits, 3-wire.
AI835A TC inputs with open circuit detection. 8 ch., (7+ ref. junction), 1 group of 8 ch., TC types B, C, D, E, J, K, L, N, R, S, T, U, -30…75 mV, 15 bits.
Analog output modules
AO810V2 With open circuit detection. 8 ch., 1 group of 8 ch., 0(4)-20 mA, 14 bits, load: max 850 Ω (short-circuit-proof).
AO815 With HART interface and open circuit
detection.
8 ch., 1 group of 8 ch., 4..20 mA, 12 bit, load: max 750 Ω (short-circuit-proof ), HART interface.
AO820 Individually galvanic isolated channels
with open circuit detection
4 ch., separate returns, isolated bipolar, ±0(2)-10 V, ±0(4)-20 mA, 12 bits + sign,
load: max 550 Ω (current) / ≥2 kΩ (voltage), short-circuit-proof.
I/O modules with intrinsic-safety interface
DI890 Individually galvanic isolated digital
input channels with wire-fault
detection.
8 ch., separate returns, 24 V d.c., current sink.
DO890 Individually galvanic isolated digital
output channels with wire-fault
detection.
4 ch., separate returns, 11 V @ 40 mA, load 150-5000 Ω, current source, short circuit-proof.
AI890 Analog inputs. 8 ch., 1 group of 8 ch., single ended with common return, 0(4)-20 mA, 12 bits, transmitter power supply
AI893 TC/RTD inputs with wire-fault
detection.
8 ch. (7 + ref. junction), 1 group of 8 ch., TC types B, C, E, J, K, L, N, R, S, T, U, -10…80 mV. RTD: Pt50-
1000, Ni100-500, Cu10-100, resistor 0-4000 Ω, 3-wire. 15 bits + sign.
AI895 Analog inputs with HART interface. 8 ch., 1 group of 8 ch., single ended with common return, 4-20 mA, 12 bits,
HART interface, transmitter power supply.
AO890 Analog outputs with open circuit
detection.
8 ch., 1 group of 8 ch., 0(4)-20 mA, 12 bits, load: max 725 Ω (short-circuit-proof).
AO895 Analog outputs with HART interface &
open circuit detection.
8 ch., 1 group of 8 ch., 4-20 mA, 12 bits, HART interface, load: max 725 Ω (short-circuit-proof).
S800L I/O modules
DI801 Digital inputs. 16 ch., 1 group of 16 ch., 24 V d.c., current sink.
DI802 Individually galvanic isolated digital
input channels.
8 ch., separate returns, 110 V d.c., 120 V a.c.
DI803 Individually galvanic isolated digital
input channels.
8 ch., separate returns, 220 V d.c., 230 V a.c.
DO801 Digital outputs. 16 ch., 1 group of 16 ch., 24 V d.c., max 0.5 A, transistor, current source, short-circuit-proof.
DO802 Individually galvanic isolated digital
output channels.
8 ch., separate returns, 24-250 V, max 2 A a.c./d.c., relay (N.O.).
AI801 Analog inputs. 8 ch., 1 group of 8 ch., single ended with common return, 0(4)-20 mA, 12 bits.
AO801 Analog outputs. 8 ch., 1 group of 8 ch., 0(4)-20 mA, 12 bits, load: max 850 Ω (short-circuit-proof).
S800 I/O modules for redundancy
DI840 Digital inputs with SOE. 16 ch., 1 group of 16 ch., 24 V d.c., current sink, extended diagnostics, transmitter power supply.
DP840 Pulse counters with wire-fault
detection.
8 ch., 1 group of 8 ch., freq. measurement or pulse counting, 0.5-20 kHz,12/24 V d.c or NAMUR,
extended diagnostics.
DO840 Digital outputs with short circuit
detection.
16 ch., 1 group of 16 ch., 24 V d.c., max. 0,5 A, current source, short-circuit-proof, extended
diagnostics.
AI843 TC inputs with open circuit detection. 8 ch. + ref. junction, 1 group of 8 ch., TC types: B, C, E, J, K, L, N, R, S, T, U, -30…75 mV, 16 bits,
extended diagnostics.
AI845 Analog inputs with HART interface. 8 ch., 1 group of 8 ch., single ended with common return, 0(4)-20 mA 0(1)-5 V, 12 bits, extended
diagnostics, HART interface, transmitter power supply.
AO845A Analog outputs with HART interface &
open circuit detection.
8 ch., 1 group of 8 ch., 4-20 mA, 12 bit, load: max 750 Ω (short-circuit-proof )
extended diagnostics, HART interface.
S800 I/O modules for SIL3
DI880 SIL3 digital inputs with SOE. 16 ch., 1 group of 16 ch., 24 V d.c., current sink, extended diagnostics, transmitter power supply, SIL3.
DO880 SIL3 digital outputs with wire-fault
detection.
16 ch., 1 group of 16 ch., 24 V d.c., max. 0.5 A, current source, short-circuit-proof,
extended diagnostics, SIL3.
AI880A SIL3 analog inputs with HART
interface.
8 ch., 1 group of 8 ch., single ended with common return, 0(4)-20 mA, 12 bit,
extended diagnostics, HART interface, transmitter power supply, SIL3.